Fire Sprinkler Requirements for Commercial Buildings
Fire Sprinkler Requirements for Commercial Buildings
903.2 Where required. Automatic sprinkler systems shall comply with this section with the following
exceptions:
1. Commercial buildings—Automatic sprinkler systems will be required in all newly constructed
buildings exceeding 3,600 square feet of fire area, any remodel or addition that changes the
footprint beyond 3,600 square feet or any single tenant expansion requiring a new certificate
of occupancy that exceeds 12,000 square feet of fire area. Whichever requirement listed in
this chapter, including exceptions, or defined in this amendment that is more restrictive will
apply. Credit will not be given for fire barrier walls with a fire resistive rating in lieu of
automatic fire sprinkler systems.
2. Townhomes—An automatic sprinkler system shall be installed in all townhouse occupancies
with more than two dwelling units per building. The automatic sprinkler system shall be
installed in accordance with NFPA 13-R to include garages, exterior balconies and attached
breezeways. Each building shall be provided with not less than a Class A roof covering.
903.2.1.1 Group A-1. An automatic sprinkler system shall be provided for group A-1 occupancies
where following conditions exists:
1. The floor area exceeds 3,600 square feet of fire area.
903.2.1.2 Group A-2. An automatic sprinkler system shall be provided for group A-2 occupancies
where the following condition exists:
1. The floor area exceeds 3,600 square feet of fire area.
903.2.1.3 Group A-3. An automatic sprinkler system shall be provided for group A-3 occupancies
where the following condition exists;
1. The floor area exceeds 3,600 square feet of fire area.
903.2.1.4 Group A-4. An automatic sprinkler system shall be provided for group A-4 occupancies
where the following condition exists:
1. The floor area exceeds 3,600 square feet of fire area.
903.2.1.6 Group B. An automatic sprinkler system shall be provided for B occupancies where the
following condition exists:
1. The floor area exceeds 3,600 square feet of fire area.
903.2.2. Group E. An automatic sprinkler system shall be provided for E occupancies where the
following condition exists:
1. The floor area exceeds 3,600 square feet of fire area.
903.2.3. Group F-1. An automatic sprinkler system shall be provided for F-1 occupancies where the
following condition exists:
1. The floor area exceeds 3,600 square feet of fire area.
903.2.3.2 Group F-2. An automatic sprinkler system shall be provided for F-2 occupancies where the
following condition exists:
1. The floor area exceeds 3,600 square feet of fire area.
903.2.6. Group M. An automatic sprinkler system shall be provided for M occupancies where
following condition exists:
1. The floor area exceeds 3,600 square feet of fire area.
903.2.8 Group S1
1. The floor area exceeds 3,600 square feet of fire area
903.2.8.1 Repair Garages
1. The floor area exceeds 3,600 square feet of fire area.
903.2.8.3 Self-service storage facility. An automatic sprinkler system shall be installed throughout all
self-service storage facilities.
903.2.9 Group S2
1. The floor area exceeds 3,600 square feet of fire area.
903.2.10.3 Buildings more than 55 feet in height. An automatic sprinkler system shall be installed
throughout buildings with a floor level, other than penthouses in compliance with Section 1509 of the
International Building Code that is located 55 feet (16764 mm) or more above the lowest level of fire
department vehicle access.
Exception:
1. Open parking structures in compliance with section 406.3 of the building code.
903.2.10.4 High-piled combustible storage. For any building with a clear height exceeding 12
feet (4572 mm), see chapter 23 to determine if those provisions apply.
903.2.10.5 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be
protected by an approved automatic fire extinguishing system.
903.3.1.1.1 Exempt locations. When approved by the code official, automatic sprinklers shall not be
required in the following rooms or areas where such . . . (bulk of section unchanged) . . . because it
is damp, of fire-resistance-rated construction or contains electrical equipment.
1. Any room where the application of water, or flame and water, constitutes a serious life or fire
hazard.
2. Any rooms or space where sprinklers are considered undesirable because of the nature of
the contents, when approved by the code official.
3 Generator and transformer rooms, under the direct control of a public utility, separated from
the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a
fire-resistance rating of not less than two hours.
Section 903.3.5 add a second paragraph to read as follows:
Water supply as required for such systems shall be provided in conformance with the supply
requirements of the respective standards; however, every fire protection system shall be
designed with a 10-psi safety factor.
Section 903.4 add a second paragraph to read as follows:
Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to
the sprinkler system and shall cause an alarm upon detection of water flow for more than 45
seconds. All control valves in the sprinkler and standpipe systems except for fire department
hose connection valves shall be electrically supervised to initiate a supervisory signal at the
central station upon tampering.
903.4.2 - Add second paragraph to read as follows:
The alarm device required on the exterior of the building shall be a weatherproof horn/strobe
notification appliance with a minimum 75 candela strobe rating, installed as close as
practicable to the fire department connection.
903.6.2 Spray booths and rooms. New and existing spray booths and spray rooms shall be
protected by an automatic fire-extinguishing system in accordance with section 1504.